Ground Flare (LRGO and SKEC)
Shutdown Items
| 1.0 |
Check purge system. (Refer to Purge Reduction checklists.) |
| 2.0 |
Remove and check pilots. (Refer to EEP checklist.) |
| 3.0 |
Inspect tips for visible deformations and weld cracks. |
| 4.0 |
For grade mounted flares, check depth of gravel cover over distribution piping, if applicable. Depth should be at least 18 in., unless otherwise specified on job drawings. |
| 5.0 |
For elevated flares, check condition of radiation shields and shield brackets, if applicable. |
| 6.0 |
Check FFG. (Refer to Ignition checklists.) |
Periodic On-line Items
| 1.0 |
Check purge system. (Refer to Purge Reduction checklists.) |
| 2.0 |
Check pilots. (Refer to EEP checklist.) |
| 3.0 |
Check for indications of burnback in the distribution piping. Burnback conditions may be identified by unusual noises, smoke, red glow on piping (usually seen at night) or visible deformations. |
| 4.0 |
Check FFG. (Refer to Ignition checklists.) |